Manual Yaskawa U1000
Input Voltage/ range 200 to 240 Vac 50/60 Hz (-15% to +10%), 380 to 480 Vac 50/60 Hz (-15% to +10%)
- Rated Input Frequency 50/60 Hz ± 3%
- Output Frequency Range 0 - 400 Hz
- Input Power Factor 0.98 min (for rated operation)
- Overload Capability Heavy Duty: 150% for 1 min, Normal Duty: 120% for 1 min
- Input/Output:Analogue Monitor 2 channel analogue output option AO-A3 −10 to +10 VDC (Res. 1/2048)
Digital Output 8 channel digital output option DO-A3 6 photo couplers (48 V, 50 mA or less), 2 relay contact outputs max 250 VAC/30 VDC, 1 A
Analogue Input 3 channel analogue input option AI-A3 −10 to +10 VDC (20 kΩ, Res. 1/8192), 4 to 20 mA (500 Ω, Res. 1/6554)
Digital Input 1 channel digital input option DI-A3 16 bit binary, 2 digit BCD + sign signal + set signal, +24 V (isolated), 8 mA 2 relay contact outputs max 250 VAC/30 VDC, 1 A
- Communication option card
CANopen SI-S3
Interface Unit CC-Link SI-C3
DeviceNET SI-N3 EtherCAT SI-ES3
EtherNET/IP SI-EN3 / SI-END3
MECHATROLINK-II SI-T3
MECHATROLINK-III SI-ET3
Modbus TCP/IP SI-EM3
POWERLINK SI-EL3
PROFIBUS-DP SI-P3
PROFINET SI-EP3
- Speed feedback:
Open Collector Type Phase A, B, and Z pulse (complementary type), max. 50 kHz (PG-B3)
Line Driver Type Phase A, B, and Z pulse (differential pulse) (RS-422), max. 300 kHz, pulse monitor output (PG-X3)